The X1366P-AGC profile for the myCNC software is presented below:
The Automatic Gas Console panel allows to set the preflow and cutflow gas pressures, as well as run the testing procedures on both of those states. The testing software PLCs are available:
- __HT_TEST_PREFLOW
main()
{
a=gvarget(7473);
if (a==0) { gvarset(7473, 1); }
else {gvarset(7473, 0); };
exit(99);
};
- __HT_TEST_CUTFLOW
main()
{
a=gvarget(7472);
if (a==0) { gvarset(7472, 1); }
else {gvarset(7472, 0); };
exit(99);
};
Next, head over to Config > Panel/Pendant > Operator Panel. Here, you can configure the connection parameters by setting the Enable checkbox to ON, as well as selecting the Serial Port number and Serial connection speed with the Hypertherrm console. Note that a UART-RS422/485 or a USB-RS422/485 adapter is required for physical communication with the AGC.
Name | Global variable | Comment |
GVAR_HT_GAS_MIXING_SETPOINT | 7467 | Mixing setpoint |
GVAR_HT_SYSTEM_ERROR | 7468 | System error code |
GVAR_HT_SYSTEM_STATUS | 7469 | System status code |
GVAR_HT_FIRMWARE_VERSION | 7471 | Firmware version (as a string variable) |
GVAR_HT_TEST_CUTFLOW_GASES | 7472 | Cutflow testing on/off |
GVAR_HT_TEST_PREFLOW_GASES | 7473 | Preflow testing on/off |
7660 | Plasma preflow pressure |
7661 | Shield preflow pressure |
7662 | Plasma cutflow pressure |
7663 | Shield cutflow pressure |